India State Factories Rules wet-bulb ceiling schedule (Kerala r.17A, Maharashtra r.22A, Madhya Pradesh r.23) — Heat Stress Screening Thresholds

The Kerala (r.17A), Maharashtra (r.22A) and Madhya Pradesh (r.23) Factories Rules set a maximum wet-bulb temperature for factory workrooms at 1.5 m above floor level: 30 C, tightened by a schedule keyed on dry-bulb temperature, with air movement of at least 30 m/min.

Browse all standards → · Evaluate every standard at once in the calculator →

Governing metric
Workroom wet-bulb temperature (C) against dry-bulb temperature (C)
Authority
State Factories Inspectorates (Kerala; Maharashtra DISH; Madhya Pradesh)
Jurisdiction
India Factories Rules
Legal status
Regulation
In force since
2001 (unverified)
Rule type
Screening Limit
Standard ID
HGC-142

Check a reading against this rule

The drag-to-check calculator needs JavaScript. Every value it can show is a row of the table below, which is computed by the same engine.

Governing formula

No standalone formula is published for this standard; see programmable logic and parameters below.

Screening thresholds

ParameterValue
wetBulbCeilingC30
minAirMovementMPerMin30
measurementHeightM1.5
scheduledryBulbFromC 30, dryBulbToC 34, maxWetBulbC 29, dryBulbFromC 35, dryBulbToC 39, maxWetBulbC 28.5, dryBulbFromC 40, dryBulbToC 44, maxWetBulbC 28, dryBulbFromC 45, dryBulbToC 47, maxWetBulbC 27.5

Programmable logic

Wet-bulb ceiling is 30 C. Dry-bulb 30-34 C: 29 C; 35-39 C: 28.5 C; 40-44 C: 28 C; 45-47 C: 27.5 C. A dry-bulb between two bands takes the value of the higher reading (e.g. 34.5 C uses the 35-39 band). If the black-globe thermometer (15 cm) reading exceeds the dry-bulb, the globe reading replaces dry-bulb. Dry-bulb below 30 C: only the 30 C ceiling applies (schedule starts at 30 C).

Dry-bulb above 47 C: schedule is silent; the 27.5 C row is applied as a conservative assumption. Screening limit: no work/rest schedule and no stop-work.

Not modelled: the Maharashtra/MP proviso that the allowed value may be exceeded to the same extent when the outside shade wet-bulb exceeds 27 C (no outside wet-bulb input); the exemption for s.15 factories and processes with unavoidably high temperatures; the 30 m/min air-movement duty is reported as a control.